Fire Alarm & Detection Systems Flashcards
7 cards from real CFI practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.
Read the first 7 Fire Alarm & Detection Systems flashcards as text
Under NFPA 72, what is the maximum allowable spacing between smoke detectors on a smooth ceiling with no obstructions?
Answer: 50 feet
NFPA 72 allows smoke detector spacing up to 50 feet between detectors on smooth ceilings.
A heat detector rated at 135°F (57°C) is classified as which type?
Answer: Fixed-temperature only
A detector rated at a specific temperature threshold (135°F) without a rate-of-rise element is a fixed-temperature detector.
Which NFPA standard governs the installation of fire alarm systems in the United States?
Answer: NFPA 72
NFPA 72, the National Fire Alarm and Signaling Code, governs the installation, inspection, testing, and maintenance of fire alarm systems.
What is the primary purpose of a 'supervisory signal' in a fire alarm system?
Answer: Alert personnel to an off-normal condition in a fire protection system
A supervisory signal indicates that a fire protection system or component (such as a sprinkler control valve) is in an off-normal condition.
Beam-type smoke detectors are best suited for protecting which type of area?
Answer: Large open areas with high ceilings such as atriums or warehouses
Projected beam smoke detectors are ideal for large open spaces with high ceilings where installing point-type detectors would be impractical.
What does a 'Class A' wiring style provide in a fire alarm system that 'Class B' does not?
Answer: Fault tolerance through a return path, allowing operation during a single open-circuit fault
Class A wiring loops back to the control panel, so a single break in the circuit does not disable devices beyond the fault point.
An inspector finds that a duct smoke detector's sampling tube is clogged with dust. What is the immediate concern?
Answer: The detector may fail to detect smoke in the HVAC duct
A clogged sampling tube prevents smoke-laden air from reaching the sensing chamber, making the detector unable to respond to a real fire event.