Refrigerant Handling & Recovery Procedures Flashcards

7 cards from real CFC practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.

Read the first 7 Refrigerant Handling & Recovery Procedures flashcards as text
  1. What is the purpose of the 'liquid recovery' method versus 'vapor recovery' when recovering refrigerant?

    Answer: Liquid recovery is faster because it transfers refrigerant mass more quickly

    Liquid recovery transfers refrigerant mass much faster than vapor recovery because liquid is denser, significantly reducing recovery time for large systems.

  2. Which of the following conditions would cause a recovery machine to short-cycle (rapid on/off cycling)?

    Answer: A kinked recovery hose restricting refrigerant flow

    A kinked or restricted recovery hose causes the recovery machine compressor to short-cycle because it cannot pull adequate refrigerant flow.

  3. Under EPA Section 608, technicians working on small appliances (less than 5 lbs of refrigerant) must use recovery equipment that captures at least what percentage of refrigerant?

    Answer: 90%

    EPA requires recovery equipment certified to capture at least 90% of the refrigerant from small appliances before disposing of or opening the system.

  4. What does the term 'recycle' mean in the context of refrigerant handling, as distinct from 'reclaim'?

    Answer: Recycle means cleaning refrigerant on-site using recovery/recycling equipment without full ARI 700 testing

    Recycling cleans refrigerant through oil separation, filtration, and moisture removal on-site but does not certify it to ARI 700 purity standards like reclamation does.

  5. A technician recovering R-410A notices the recovery cylinder is getting hot to the touch during the process. What is the MOST likely cause?

    Answer: The high heat of compression from the recovery machine is warming the cylinder

    Heat from the recovery machine's compression process transfers to the recovery cylinder as refrigerant vapor is compressed and condensed into it, causing it to warm.

  6. Which refrigerant requires special low-loss fittings on all service hoses and equipment to comply with EPA Section 608?

    Answer: All refrigerants covered under Section 608

    EPA Section 608 requires low-loss fittings on all hoses and equipment used to service any appliance containing refrigerants covered by the regulation.

  7. After completing refrigerant recovery, a technician must verify completeness by checking the system pressure. For equipment manufactured after November 15, 1993 with a charge between 50 and 200 lbs, what is the required final system pressure for high-pressure refrigerants?

    Answer: 10 psig

    EPA regulations require a final recovery level of 10 psig for high-pressure appliances manufactured after November 15, 1993 containing 50-200 lbs of refrigerant.