  1. According to EPA Section 608, what is the required vacuum level before opening a system for non-major repairs on appliances with more than 200 pounds of refrigerant?

    Answer: 4 inches Hg vacuum

    EPA regulations require a 4-inch Hg vacuum for appliances containing more than 200 pounds of refrigerant before opening for non-major repairs.

  2. Which of the following refrigerants requires recovery equipment to be certified to a HIGHER standard due to its flammability?

    Answer: R-290 (propane)

    R-290 (propane) is an A3 flammable refrigerant requiring equipment specifically rated for flammable refrigerant handling.

  3. When recovering a blend refrigerant such as R-410A, which method is MOST effective for recovering both liquid and vapor phases efficiently?

    Answer: Liquid recovery from the high side followed by vapor recovery from the low side

    Recovering liquid first from the high side, then vapor from the low side maximizes efficiency and maintains blend composition.

  4. A recovery cylinder bearing a yellow top and gray body is designated for use with:

    Answer: Any recovered refrigerant

    The standard yellow-top gray-body color coding designates a cylinder approved for recovered refrigerants of any type.

  5. What is the purpose of the two-stage recovery process used with large commercial systems?

    Answer: To recover liquid refrigerant first for speed, then capture remaining vapor

    The two-stage process recovers bulk liquid quickly, then uses the recovery machine to capture remaining low-pressure vapor.

  6. An oil-less recovery compressor is MOST advantageous when recovering refrigerant that:

    Answer: Will be recycled on-site and must not be contaminated with compressor oil

    Oil-less compressors prevent oil carryover into the recovered refrigerant, which is critical when the refrigerant will be recycled for reuse.

  7. If a recovery cylinder's pressure gauge shows a pressure higher than expected for the ambient temperature after recovery, the technician should suspect:

    Answer: The cylinder contains non-condensable gases such as air or nitrogen

    Non-condensable gases like air or nitrogen raise cylinder pressure above the saturation pressure expected at a given temperature.