Compressor & Component Diagnostics Flashcards

7 cards from real CFC practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.

Read the first 7 Compressor & Component Diagnostics flashcards as text
  1. A scroll compressor exhibits abnormal noise during startup but runs quietly at full speed. What is the most likely cause?

    Answer: Refrigerant slugging due to liquid floodback

    Liquid refrigerant entering a scroll compressor during startup causes slugging noise as the incompressible fluid damages scroll wraps.

  2. When diagnosing a reciprocating compressor with low suction pressure and low discharge pressure, which condition is most likely?

    Answer: Worn or broken valve reeds

    Broken or worn valve reeds cause low compression efficiency, resulting in both low suction and low discharge pressure simultaneously.

  3. A technician measures a compressor's amp draw at 85% of the rated full-load amps with normal pressures. This indicates:

    Answer: Normal operation within acceptable tolerance

    Amp draw at 85% of rated FLA with normal pressures indicates the compressor is operating normally within standard tolerance bands.

  4. What does a high superheat reading at the compressor suction combined with normal subcooling at the condenser outlet most likely indicate?

    Answer: TXV or metering device starving the evaporator

    High superheat with normal subcooling indicates insufficient refrigerant flow through the metering device, starving the evaporator of refrigerant.

  5. A compressor trips on its internal overload repeatedly on hot days but resets overnight. The most probable diagnosis is:

    Answer: High ambient temperature causing high head pressure overloading the motor

    High ambient temperatures elevate condensing pressure, increasing compressor motor load and amp draw until the overload trips.

  6. When performing a megohm test on a compressor motor, a reading of 0.5 megohms indicates:

    Answer: Marginal insulation that may indicate moisture or contamination

    A megohm reading of 0.5 MΩ indicates marginal insulation resistance, suggesting moisture contamination or degrading motor insulation.

  7. A technician finds oil logged in the evaporator of a CFC system. Which compressor condition most commonly causes this problem?

    Answer: Worn compressor rings allowing oil to bypass into the refrigerant circuit

    Worn piston rings in a reciprocating compressor allow excessive oil to pass into the refrigerant stream, resulting in oil accumulation in the evaporator.