Plan Review & Permit Processing Flashcards

7 cards from real CEI practice questions. Tap to flip, then mark Knew It or Still Learning โ€” missed cards come back until you master them.

Read the first 7 Plan Review & Permit Processing flashcards as text
  1. A plan reviewer is checking an electrical drawing for a swimming pool installation. Which NEC article is most critical to apply?

    Answer: Article 680

    NEC Article 680 governs swimming pools, fountains, and similar installations, covering bonding, GFCI protection, and equipment placement requirements.

  2. During plan review for a solar photovoltaic system, which NEC article is the primary reference for the DC wiring methods and equipment?

    Answer: Article 690

    NEC Article 690 specifically governs solar photovoltaic systems, covering wiring, disconnect requirements, and interconnection to utility systems.

  3. A permit application for an EV charging station is submitted. Which NEC article should the plan reviewer primarily consult?

    Answer: Article 625

    NEC Article 625 governs electric vehicle charging systems, addressing equipment, wiring methods, and installation requirements.

  4. When reviewing plans for a healthcare facility, which NEC article addresses the essential electrical system requirements for hospitals?

    Answer: Article 517

    NEC Article 517 governs healthcare facilities, including essential electrical system requirements for life safety, critical, and equipment branches.

  5. A plan reviewer finds that proposed conduit runs in a parking garage are not identified as suitable for wet locations. What correction should be required?

    Answer: Specify conduit types listed for wet locations such as RMC, IMC, or Schedule 80 PVC

    Parking garages are classified as wet locations; conduit systems must be listed for wet location use per NEC wiring method requirements.

  6. On a commercial plan, the electrical room dimensions show the transformer taking up all available space with no working clearances. Per NEC 110.26, what is the minimum required clearance in front of the transformer?

    Answer: 3 feet for equipment up to 150V to ground

    NEC 110.26(A)(1) requires a minimum of 3 feet of working clearance for equipment rated up to 150V to ground (Condition 1).

  7. Which of the following is a valid reason for an AHJ to require electrical plans to be prepared by a licensed electrical engineer?

    Answer: The project complexity or occupancy type exceeds what the AHJ deems appropriate for non-engineered submissions

    The AHJ has authority to require PE-stamped drawings based on project complexity, occupancy classification, or other factors warranting engineering oversight.