Under the NEC, what is the maximum allowed voltage drop for branch circuits to ensure reasonable efficiency of operation?
Answer: 3%
NEC 210.19(A) informational note recommends limiting branch circuit voltage drop to 3% for reasonable efficiency.
Which NEC article governs the installation of patient care areas in health care facilities?
Answer: Article 517
NEC Article 517 covers electrical wiring and equipment installed in health care facilities including patient care areas.
According to the NEC, a 20-ampere, 125-volt receptacle installed outdoors must be protected by which of the following?
Answer: GFCI
NEC 210.8(A) requires GFCI protection for 125-volt receptacles installed in outdoor locations.
What is the minimum clearance required by the NEC between the top of a service entrance conductor and a window that opens?
Answer: 3 feet
NEC 230.9(A) requires service conductors to be at least 3 feet from windows that open.
Which NEC article specifically addresses the installation of solar photovoltaic (PV) systems?
Answer: Article 690
NEC Article 690 covers the installation of solar photovoltaic energy systems.
Under NEC 300.4, where a raceway or cable passes through a wood structural member, a steel plate of at least what thickness is required when the edge is within 1-1/4 inches of the nearest edge?
Answer: 1/8 inch
NEC 300.4(A)(1) requires a steel plate at least 1/8 inch thick to protect cables or raceways from nails and screws.
The NEC requires that equipment grounding conductors be identified by which color when insulated?
Answer: Green or bare
NEC 250.119 requires equipment grounding conductors to be identified by green insulation, green with yellow stripe, or bare copper.