Wiring Methods and Materials Flashcards
7 cards from real CEA practice questions. Tap to flip, then mark Knew It or Still Learning โ missed cards come back until you master them.
Read the first 7 Wiring Methods and Materials flashcards as text
When conductors of different systems share the same raceway, they must all be insulated for the:
Answer: Highest voltage present
NEC 300.3(C)(1) requires all conductors sharing a raceway to be insulated for the highest voltage present in that raceway.
What is the color code for the high-leg (wild leg) conductor in a 4-wire, 3-phase delta system?
Answer: Orange
NEC 230.56 and 408.3(F) require the high-leg conductor in a 3-phase delta system to be identified with orange color.
Electrical metallic tubing (EMT) is NOT permitted to be used in which condition?
Answer: Subject to severe physical damage
NEC 358.12 prohibits EMT where it will be subject to severe physical damage due to its thin-wall construction.
Type MC cable used for wiring in an accessible ceiling plenum space used for environmental air must be which type?
Answer: MC cable with a smooth or corrugated aluminum sheath or listed plenum cable
NEC 330.10(A)(11) and 300.22 require cables in air-handling plenums to be plenum-rated or have a metallic sheath that limits flame and smoke spread.
A 2-inch rigid metal conduit (RMC) must have a support within what distance of each box, cabinet, or conduit fitting?
Answer: 3 feet
NEC 344.30(B)(1) requires RMC to be supported within 3 feet of each outlet box, junction box, device box, cabinet, conduit body, or other conduit termination.
Which statement about aluminum conductors smaller than No. 8 AWG is correct under the NEC?
Answer: They are not permitted for branch circuit wiring
NEC 310.106(B) prohibits solid aluminum conductors smaller than No. 8 AWG for branch circuit wiring due to connection failure risks.
When pulling wire through conduit, the maximum pulling tension for copper conductors is based on a stress of:
Answer: 0.008 lb/circular mil
Industry practice limits conductor pulling tension to 0.008 lb per circular mil of cross-sectional area to avoid stretching or damaging copper conductors.