Wiring Methods and Materials Flashcards

7 cards from real CEA practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.

Read the first 7 Wiring Methods and Materials flashcards as text
  1. What is the maximum number of 90-degree bends allowed in a single run of conduit between pull points according to the NEC?

    Answer: Four 90-degree bends

    NEC 358.26 limits conduit runs to a maximum of four quarter bends (360 degrees total) between pull points.

  2. Which wiring method is specifically listed for use in wet locations and is identified by a 'W' rating?

    Answer: TW

    TW conductors have a 'W' suffix indicating they are rated for wet locations, with a 60°C temperature rating.

  3. When installing flexible metal conduit (FMC), what is the minimum trade size permitted for general use?

    Answer: 1/2 inch

    NEC 348.20 permits 3/8-inch FMC only in limited applications; 1/2-inch is the minimum for general use.

  4. Rigid PVC conduit (Schedule 40) must be supported at intervals not exceeding how many feet for trade sizes 1/2 to 1 inch?

    Answer: 3 feet

    NEC 352.30 requires Schedule 40 PVC conduit 1/2 to 1 inch to be supported every 3 feet.

  5. Which conductor insulation type is rated for use in both wet and dry locations at 90°C?

    Answer: THWN-2

    THWN-2 is rated 90°C in both wet and dry locations, making it one of the most versatile insulation types.

  6. What material is type AC cable (armored cable) armor made from?

    Answer: Steel spiral wrap

    Type AC cable uses a spiral-wound steel armor that provides mechanical protection and serves as a ground return path.

  7. When using metal wireways, the sum of cross-sectional areas of all contained conductors must not exceed what percentage of the wireway's interior cross-section?

    Answer: 40%

    NEC 376.22 limits conductors in metal wireways to 20% fill at splices/taps, and 40% fill for through-conductors.