  1. In an energy audit context, 'phantom loads' (also called standby or vampire loads) refer to:

    Answer: Energy consumed by plug-in devices while switched off or in standby mode

    Phantom loads can account for 5–10% of residential and small commercial electricity use; smart power strips and occupancy-based controls reduce them.

  2. An energy auditor recommends a variable frequency drive (VFD) on a constant-volume pump. The energy savings potential follows the affinity laws, meaning a 20% speed reduction yields approximately:

    Answer: 49% reduction in power consumption (cube law relationship)

    Per the affinity laws, pump power varies with the cube of speed: (0.80)³ = 0.512, meaning a 20% speed reduction reduces power by approximately 49%.

  3. When reviewing a building's energy model during an audit, the auditor finds that the simulated EUI closely matches the actual utility EUI. This means the model is:

    Answer: Calibrated and can be used to reliably predict savings from proposed energy conservation measures

    A calibrated energy model that matches actual utility data is a reliable tool for predicting ECM savings and is the foundation of investment-grade (Level III) audits.

  4. A 'short-circuit factor' in duct leakage testing refers to:

    Answer: Supply air leaking directly into return air pathways before conditioning occupied spaces

    Supply-to-return duct leakage short-circuits conditioned air, reducing HVAC effectiveness and forcing the system to work harder to maintain setpoints.

  5. During a renewable energy feasibility assessment as part of an energy audit, which factor is MOST critical in evaluating a rooftop solar PV installation?

    Answer: Roof orientation, tilt angle, and shading analysis to determine annual solar irradiance

    Solar resource quality—determined by orientation, tilt, and shading—directly governs PV system output and is the primary technical determinant of project viability.

  6. An energy auditor uses a 'load disaggregation' technique. What is the primary goal?

    Answer: To break down total building energy use into contributions from individual end uses (HVAC, lighting, plug loads, etc.)

    Load disaggregation allocates metered consumption to specific end uses, enabling auditors to prioritize ECMs that target the largest energy consumers.

  7. Under the Energy Policy Act (EPAct) and related standards, which type of building is REQUIRED to benchmark energy performance using ENERGY STAR Portfolio Manager?

    Answer: Federal buildings over 5,000 square feet must report energy use annually under federal mandates

    Federal agencies are required by law (EPAct 2005, EO 13693) to benchmark all buildings over 5,000 sf in ENERGY STAR Portfolio Manager and report annually.