CEA Motor Controls and Control Circuits Questions and Answers Flashcards

6 cards from real CEA practice questions. Tap to flip, then mark Knew It or Still Learning โ€” missed cards come back until you master them.

Read the first 6 CEA Motor Controls and Control Circuits Questions and Answers flashcards as text
  1. In a wye-delta reduced-voltage starter, what is the motor connection at startup?

    Answer: Wye (star)

    During startup the motor is connected in wye, which applies approximately 58% of line voltage to each winding, reducing inrush current to about one-third.

  2. What NEC article primarily covers the installation of motor circuits and controllers?

    Answer: Article 430

    NEC Article 430 covers motors, motor circuits, and controllers, including conductor sizing, overcurrent protection, and disconnecting means requirements.

  3. According to the NEC, the branch-circuit short-circuit and ground-fault protective device for a motor is permitted to be sized larger than the conductor ampacity. What is the maximum percentage of full-load current allowed for an inverse-time breaker protecting a Design B motor?

    Answer: 250%

    NEC Table 430.52 allows an inverse-time circuit breaker for a Design B squirrel-cage motor to be sized up to 250% of the motor's full-load current.

  4. What is the minimum disconnect switch ampere rating required for a motor branch circuit?

    Answer: 125% of the motor full-load current

    Per NEC 430.110, the motor disconnecting means must have an ampere rating of at least 115% of the motor's full-load current.

  5. Which type of motor control device uses a bimetallic strip or melting alloy (solder pot) to sense motor overload?

    Answer: Thermal overload relay

    Thermal overload relays use a bimetallic strip or melting alloy element that responds to heat generated by excess current flowing through it.

  6. When sizing overload relay heaters for a motor with a service factor of 1.15, the overload device must not exceed what percentage of the motor's full-load current?

    Answer: 125%

    Per NEC 430.32(A)(1), for motors with a marked service factor of 1.15 or greater, the overload device must not exceed 125% of the motor's full-load current.