Data Center Operations and Maintenance Flashcards
7 cards from real CDCP practice questions. Tap to flip, then mark Knew It or Still Learning โ missed cards come back until you master them.
Read the first 7 Data Center Operations and Maintenance flashcards as text
During a preventive maintenance window, a UPS battery string fails a capacity test at 78% of rated capacity. What is the recommended action?
Answer: Replace the entire battery string immediately
A battery string failing below 80% of rated capacity is the standard threshold for immediate replacement to ensure reliable backup power.
Which metric is most critical when evaluating the efficiency of a data center cooling system?
Answer: Cooling system COP (Coefficient of Performance)
COP measures the ratio of cooling output to energy input, directly reflecting cooling system efficiency.
A data center operations team is implementing a change to add a new PDU. Which document must be updated FIRST before energizing the new PDU?
Answer: Single-line electrical diagram
The single-line electrical diagram must be updated first as it is the authoritative reference for safe electrical work and lockout/tagout procedures.
What is the purpose of a 'hot aisle containment' strategy in data center operations?
Answer: Prevent mixing of cold supply air with hot exhaust air
Hot aisle containment captures server exhaust air directly and routes it to cooling units, preventing recirculation and improving cooling efficiency.
A facility manager notices the PUE has risen from 1.45 to 1.68 over three months. What is the MOST likely cause to investigate first?
Answer: Cooling system inefficiency or failure
A rising PUE with stable IT load typically indicates cooling overhead has increased, pointing to cooling system degradation or misconfiguration.
Which practice BEST supports 'lights-out' or remote operations in a data center?
Answer: Deploying DCIM with remote monitoring and alerting
DCIM (Data Center Infrastructure Management) provides real-time visibility, alerting, and remote control capabilities essential for lights-out operations.
During a fire suppression system inspection, the clean agent cylinder weight is found to be 5% below the minimum fill level. What action should be taken?
Answer: Refill the cylinder to full capacity before returning to service
A cylinder below minimum fill level must be recharged before returning to service to ensure the system can deliver the required agent concentration.