Troubleshooting & Maintenance of Control Systems Flashcards

7 cards from real CCST practice questions. Tap to flip, then mark Knew It or Still Learning โ€” missed cards come back until you master them.

Read the first 7 Troubleshooting & Maintenance of Control Systems flashcards as text
  1. A control valve with a positioner consistently stops 5% short of the commanded position throughout its stroke. This is most indicative of:

    Answer: Positioner feedback linkage slippage or incorrect cam

    A consistent gain error across the full stroke (always 5% short) points to a mechanical error in the positioner feedback linkage or an incorrectly adjusted cam.

  2. During loop checkout, a technician applies 4 mA to a controller input and the display reads 1.2% instead of 0%. The most appropriate correction is:

    Answer: Perform a zero trim on the transmitter or input card

    A small offset at the live zero (4 mA) with no corresponding process variable indicates a zero calibration error that should be corrected with a zero trim.

  3. What does a negative loop gain indicate in a feedback control system during troubleshooting?

    Answer: The controller action (direct/reverse) is set incorrectly

    Negative loop gain (output moves in the wrong direction relative to error) means the controller action (direct vs. reverse acting) is set opposite to what the process requires.

  4. A technician is calibrating a RTD temperature transmitter. The measured resistance at ice point is 2 ohms higher than expected. What is the likely cause?

    Answer: Lead wire resistance not compensated (2-wire RTD used without compensation)

    In a 2-wire RTD connection, lead wire resistance adds directly to the measured resistance; a 3- or 4-wire configuration must be used or lead resistance must be compensated.

  5. An analog control loop passes loop current through a junction box where several connections are made. Intermittent signal drops to 0 mA are observed. What is the first thing to inspect?

    Answer: Junction box terminal connections for corrosion or loose terminations

    Intermittent drops to 0 mA suggest a momentary open circuit, and the highest-probability location in a loop is corroded or loose terminals inside the junction box.

  6. Which document should a technician consult to determine the correct fail-safe position of a control valve before performing maintenance?

    Answer: P&ID (Piping and Instrumentation Diagram)

    The P&ID specifies valve failure positions (fail-open, fail-closed, fail-in-place) using standard symbology and is the primary reference for safe valve maintenance.

  7. A cascade control system's secondary (inner) loop is responding poorly, causing the primary loop to oscillate. What is the recommended corrective sequence?

    Answer: Break the cascade and tune the secondary loop independently, then re-engage

    Best practice is to tune inner-loop controllers independently in manual mode before engaging the cascade so that the outer loop sees a well-behaved inner loop.