โ† All CCI Flashcard Decks

Fire Protection & Life Safety Flashcards

7 cards from real CCI practice questions. Tap to flip, then mark Knew It or Still Learning โ€” missed cards come back until you master them.

Read the first 7 Fire Protection & Life Safety flashcards as text
  1. A fire-rated wall assembly must be tested in accordance with which standard?

    Answer: ASTM E119

    ASTM E119 (Standard Test Methods for Fire Tests of Building Construction and Materials) is the standard used to determine fire-resistance ratings of wall assemblies.

  2. What is the maximum travel distance to an exit in a non-sprinklered business occupancy under IBC?

    Answer: 200 feet

    IBC allows a maximum travel distance of 200 feet to an exit in non-sprinklered business occupancies.

  3. When inspecting a dry pipe sprinkler system, the inspector should verify that the air pressure in the system is maintained at what relationship to the water supply pressure?

    Answer: At a ratio ensuring the differential prevents premature opening

    Dry pipe valves use a differential ratio (typically 6:1 air-to-water pressure) so the air pressure needed to hold the clapper closed is much lower than the water supply pressure.

  4. Under IBC, a common path of egress travel in a sprinklered building with an occupant load of 30 or fewer may not exceed:

    Answer: 100 feet

    IBC permits a common path of egress travel up to 100 feet in sprinklered buildings where the occupant load does not exceed 30.

  5. Which type of fire extinguisher is appropriate for use on a Class K (cooking oil and grease) fire?

    Answer: Wet chemical extinguisher

    Wet chemical extinguishers are specifically designed for Class K fires involving cooking oils and greases in commercial cooking equipment.

  6. What is the primary purpose of a fire damper in an HVAC duct penetrating a fire-rated wall?

    Answer: Prevent flame and hot gases from passing through the duct opening

    Fire dampers close automatically upon heat activation to prevent fire (flames and hot gases) from traveling through ductwork penetrations in fire-rated assemblies.

  7. The International Fire Code requires portable fire extinguishers to be inspected at minimum how often?

    Answer: Monthly

    The IFC requires portable fire extinguishers to receive a visual inspection at least monthly to verify they are in their designated location, unobstructed, and show no obvious defects.