What is the primary purpose of conducting a walk test on a motion detector after installation?
Answer: To verify the detector's field of view covers the intended protected area
A walk test confirms that movement within the designated coverage zone actually triggers an alarm response.
During inspection of a two-wire smoke detector circuit, the technician reads 0 V across the loop. What is the most likely cause?
Answer: An open circuit or broken wire on the loop
Zero volts on a supervised loop indicates an open circuit, which breaks the supervisory current path.
A newly installed glass-break detector fails its functional test when a test instrument is used but responds when glass is actually broken nearby. What is the likely issue?
Answer: The test instrument frequency or SPL does not match the detector's sensitivity range
Glass-break simulators must match the detector's listed frequency response and sound pressure level to produce a valid result.
Which NFPA 72 table governs the inspection, testing, and maintenance frequency for manual pull stations?
Answer: Table 14.3.1
NFPA 72 Table 14.3.1 lists required ITM frequencies for all fire alarm system components including manual pull stations.
A fire alarm system inspection reveals that a sprinkler waterflow switch has a 90-second retard setting. Why might this require review?
Answer: NFPA 72 limits retard to 90 seconds maximum, so any setting at or beyond this needs AHJ approval
NFPA 72 allows up to 90 seconds of retard for waterflow switches; settings at the limit should be confirmed with the AHJ.
What color is the standard wiring insulation used for the positive leg of a four-wire smoke detector power circuit in most US installations?
Answer: Red
Industry convention assigns red to the positive power conductor and black to negative in fire alarm wiring.
When testing notification appliances, the measured sound level at a sleeping area pillow must meet which minimum dBA requirement per NFPA 72?
Answer: 75 dBA at the pillow
NFPA 72 requires a minimum of 75 dBA measured at the pillow level in sleeping areas to ensure audibility during sleep.