โ† All CAT Flashcard Decks

CAT Codes, Standards, and Regulations Flashcards

6 cards from real CAT practice questions. Tap to flip, then mark Knew It or Still Learning โ€” missed cards come back until you master them.

Read the first 6 CAT Codes, Standards, and Regulations flashcards as text
  1. Under NFPA 72, what is the minimum battery backup duration required for a supervised fire alarm system?

    Answer: 24 hours in standby plus 5 minutes in alarm

    NFPA 72 requires fire alarm systems to operate for at least 24 hours on battery standby followed by 5 minutes of full alarm operation.

  2. What does NEC Article 760 regulate?

    Answer: Fire alarm systems wiring and equipment

    NEC Article 760 covers the installation of fire alarm systems, including power-limited and non-power-limited wiring methods and cable types.

  3. What is UL 681 the standard for?

    Answer: Installation and classification of burglar and holdup alarm systems

    UL 681 covers the installation requirements and performance classifications for burglar alarm and holdup alarm systems in residential and commercial applications.

  4. What must occur before a newly installed fire alarm system can be placed into service?

    Answer: Acceptance testing witnessed by the AHJ or their representative

    NFPA 72 requires a formal acceptance test of all system functions performed in the presence of, or approved by, the AHJ before a fire alarm system goes live.

  5. Under UL 827, how often must central station operators be recertified?

    Answer: Every 2 years

    UL 827 requires central station operators to be recertified every two years to maintain UL-listed central station status.

  6. What does the NFPA 72 'pathway survivability' requirement address?

    Answer: Fire alarm circuit wiring must remain operational during a fire in certain building types

    Pathway survivability requires that alarm circuit wiring in high-rise and similar buildings be protected so it continues to function during a fire event.