  1. What is the main purpose of maintaining superheat at the outlet of a direct-expansion (DX) evaporator?

    Answer: To ensure only vapor returns to the compressor

    Superheat confirms all liquid has boiled off, protecting the compressor from liquid slugging.

  2. Why does a flooded evaporator generally transfer heat better than a DX evaporator of the same size?

    Answer: Nearly all of its internal surface is wetted with liquid refrigerant

    Liquid-wetted surfaces have far higher heat transfer coefficients than surfaces contacting superheated vapor.

  3. Heavy frost accumulation on an air-cooling evaporator coil typically causes which condition?

    Answer: Reduced airflow and a falling suction pressure

    Frost insulates the coil and blocks airflow, so less heat is absorbed and suction pressure drops.

  4. In a hot gas defrost system, what heat source melts the frost from the evaporator coil?

    Answer: Compressor discharge vapor routed into the coil

    Hot gas defrost sends high-pressure discharge vapor into the coil, where it condenses and releases heat.

  5. An evaporative condenser rejects most of its heat by which mechanism?

    Answer: Evaporation of spray water over the coil

    Evaporating water absorbs large amounts of latent heat from the refrigerant inside the coil.

  6. Non-condensable gases trapped in a condenser most directly cause which problem?

    Answer: Abnormally high head pressure

    Non-condensables occupy condenser surface and add their partial pressure, raising head pressure.

  7. What is the main operating penalty of running a refrigeration system at a higher-than-necessary condensing pressure?

    Answer: Increased compressor power per ton of refrigeration

    A higher compression ratio requires more horsepower per ton and lowers efficiency.