  1. A compressor is short-cycling (turning on and off rapidly). What is the most common cause?

    Answer: Incorrect pressure control setpoint differential or refrigerant undercharge

    Short-cycling is often caused by a pressure control with too narrow a differential (cut-in too close to cut-out) or low refrigerant charge causing rapid pressure swings.

  2. What does an abnormally high compressor amp draw combined with low suction pressure indicate?

    Answer: Possible liquid slugging or mechanical issue within the compressor

    High amp draw with low suction pressure can indicate liquid slugging, worn compressor internals, or tight bearings, all of which cause the motor to work harder than normal.

  3. Moisture contamination in a refrigeration system most commonly causes what problem in the expansion device?

    Answer: Ice formation that blocks or partially freezes the expansion valve orifice

    Moisture in the refrigerant freezes at the expansion device orifice where temperature and pressure drop sharply, causing intermittent or permanent blockage and starving the evaporator.

  4. When troubleshooting an ammonia system that is not reaching its design suction temperature, what should be checked first?

    Answer: Refrigerant charge level and expansion device operation

    Insufficient refrigerant charge or a malfunctioning expansion device are the most common reasons a system cannot reach its design suction temperature, making these the first things to check.

  5. What does a continuously running compressor that never shuts off, combined with a warm refrigerated space, most likely indicate?

    Answer: Insufficient refrigeration capacity — possible refrigerant loss, dirty coils, or excessive load

    A compressor that runs continuously without achieving the setpoint indicates the system lacks sufficient capacity, which may be due to refrigerant loss, fouled heat exchangers, or an unusually high heat load.

  6. Excessive vibration in a reciprocating ammonia compressor is best diagnosed using which method?

    Answer: Visual inspection combined with vibration analysis and listening for unusual mechanical noises

    Vibration analysis and listening for unusual sounds (knocking, rattling) combined with visual inspection help identify loose mounts, worn bearings, valve issues, or liquid slugging causing the vibration.