← All Building Engineering Flashcard Decks

Mechanical Engineering Flashcards

7 cards from real Building Engineering practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.

Read the first 7 Mechanical Engineering flashcards as text
  1. What does the MERV rating system classify for HVAC air filters?

    Answer: Minimum efficiency reporting value for particle capture efficiency

    MERV (Minimum Efficiency Reporting Value) rates filters from 1–16 based on their ability to capture particles of specific sizes, with higher numbers indicating finer filtration.

  2. When sizing an expansion tank for a closed hydronic system, what is the primary variable the tank must accommodate?

    Answer: Volume change of water as it heats from fill temperature to operating temperature

    Water expands as it heats; the expansion tank provides a sealed air cushion to absorb this volume increase and keep system pressure within design limits.

  3. According to ASHRAE 90.1 energy code, what control is required for HVAC systems serving spaces with variable occupancy to reduce energy use during unoccupied hours?

    Answer: Occupancy scheduling with setback temperature control

    ASHRAE 90.1 requires programmable setback controls that reduce heating and cooling set points during unoccupied periods, reducing energy consumption.

  4. What is 'hydronic balancing' and why is it performed on a new building's heating/cooling water system?

    Answer: Adjusting flow rates at each terminal to match design values so all zones receive adequate capacity

    Hydronic balancing adjusts balancing valves so each coil or terminal receives its design flow rate, preventing overflowing near terminals and starving remote ones.

  5. A mechanical engineer specifies 'low-leakage' dampers in a pressurized air system. Which AMCA rating class would meet the most stringent leakage requirement?

    Answer: AMCA Class I

    AMCA Class I dampers have the lowest permissible leakage rate, making them appropriate for critical pressurized applications like smoke control and clean rooms.

  6. In a steam heating system, what is the primary function of a steam trap?

    Answer: Prevent steam from passing while allowing condensate and air to discharge

    Steam traps automatically discharge condensate and non-condensable gases from the steam space while blocking live steam from escaping, maintaining system efficiency.

  7. What mechanical property is evaluated when specifying pipe hangers to prevent vibration transmission from pumps to a building structure?

    Answer: Spring isolator static deflection

    Spring isolators for pipe hangers are specified by static deflection; greater deflection provides better isolation of low-frequency pump and pipe vibration from the structure.