A specification requires air filters rated per ASHRAE Standard 52.2. Which rating metric does that standard produce?
Answer: MERV (Minimum Efficiency Reporting Value)
ASHRAE 52.2 tests particle-size removal efficiency and reports the result as a MERV of 1 to 16.
Under the ASHRAE 62.1 Ventilation Rate Procedure, the breathing-zone outdoor airflow (Vbz) combines which two components?
Answer: A per-person rate (Rp) and a per-floor-area rate (Ra)
Vbz = Rp × Pz + Ra × Az, so it accounts for both occupant-related and building-related contaminants.
Which ASHRAE standard is the Safety Standard for Refrigeration Systems?
Answer: Standard 15
ASHRAE 15 covers the safe design, construction, installation and operation of refrigeration systems.
Under ASHRAE Standard 34, what does refrigerant safety group A2L mean?
Answer: Lower toxicity, lower flammability (mildly flammable)
'A' means lower toxicity, and '2L' is the mildly flammable subclass with a burning velocity of 10 cm/s or less.
ASHRAE Standard 55 commonly defines an acceptable thermal environment as one with a predicted percentage dissatisfied (PPD) below what value?
Answer: 10%
A PMV between -0.5 and +0.5 corresponds to a PPD under 10%, which is the Standard 55 comfort criterion.
A controls specification calls for interoperability per ASHRAE Standard 135. What protocol is that?
Answer: BACnet
ASHRAE 135 defines BACnet, a data communication protocol for building automation and control networks.
Which ASHRAE standard sets requirements for managing Legionellosis risk in building water systems?
Answer: Standard 188
ASHRAE 188 requires a water management program to reduce the risk of Legionella in building water systems.