In the ASHRAE 62.1 Ventilation Rate Procedure, how is breathing zone outdoor airflow (Vbz) calculated?
Answer: Vbz = Rp·Pz + Ra·Az
Vbz sums a people component (Rp × zone population) and an area component (Ra × zone floor area).
Per ASHRAE 62.1, what are the default people and area outdoor air rates for a typical office space?
Answer: 5 cfm/person and 0.06 cfm/ft²
Table 6-1 of 62.1 lists office space at Rp = 5 cfm/person and Ra = 0.06 cfm/ft².
What zone air distribution effectiveness (Ez) does ASHRAE 62.1 assign to ceiling supply of warm air at least 15°F above space temperature with ceiling return?
Answer: 0.8
Warm air supplied and returned at the ceiling tends to stratify, so 62.1 assigns Ez = 0.8.
In a multiple-zone recirculating system under ASHRAE 62.1, how is occupant diversity (D) defined?
Answer: System population divided by the sum of peak zone populations
D = Ps / ΣPz, reflecting that not all zones peak at the same time.
Which ASHRAE 62.1 compliance path lets a designer reduce outdoor air by using air cleaning, based on contaminant mass balance and target concentrations?
Answer: Indoor Air Quality Procedure
The IAQ Procedure is performance-based and credits air cleaning toward meeting contaminant limits.
Under ASHRAE 62.1, what minimum separation distance is required between an outdoor air intake and a Class 4 air exhaust outlet?
Answer: 30 ft
Table 5-1 requires 30 ft separation from Class 4 (highly objectionable) exhaust.
ASHRAE 62.1 requires mechanically cooled systems to limit space relative humidity to what maximum at the peak outdoor dew point design condition?
Answer: 65%
Section 5.9 sets a 65% RH limit to reduce microbial growth risk.