HVAC System Design and Operation Flashcards
7 cards from real ASHRAE practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.
Read the first 7 HVAC System Design and Operation flashcards as text
A chiller runs at a COP of 6.0. What is its efficiency in kW/ton, approximately?
Answer: 0.59 kW/ton
kW/ton = 3.517 / COP = 3.517 / 6.0 ≈ 0.59.
What does a thermostatic expansion valve (TXV) control directly?
Answer: Evaporator outlet superheat
A TXV meters refrigerant to hold a set superheat at the evaporator outlet.
Where is liquid subcooling measured in a vapor-compression system?
Answer: At the condenser outlet or liquid line
Subcooling is the saturated condensing temperature minus the actual liquid line temperature.
How does an air-source heat pump typically defrost its outdoor coil?
Answer: It reverses the cycle with the reversing valve so the outdoor coil works as a condenser
Switching briefly to cooling mode sends hot gas to the outdoor coil and melts the frost.
When is a waterside economizer most useful?
Answer: When outdoor wet-bulb is low enough for tower water to cool the chilled water loop through a heat exchanger
Cold tower water passes through a plate-and-frame heat exchanger to give free cooling with the chillers off or unloaded.
How does an enthalpy (total energy) recovery wheel differ from a sensible-only wheel?
Answer: It transfers both sensible heat and moisture between airstreams
A desiccant coating lets the wheel move moisture as well as heat.
What is a key design benefit of a dedicated outdoor air system (DOAS)?
Answer: It separates ventilation and latent load handling from the zone sensible cooling equipment
DOAS conditions all ventilation air on its own, so terminal units can deal mainly with sensible loads.