  1. A chiller runs at a COP of 6.0. What is its efficiency in kW/ton, approximately?

    Answer: 0.59 kW/ton

    kW/ton = 3.517 / COP = 3.517 / 6.0 ≈ 0.59.

  2. What does a thermostatic expansion valve (TXV) control directly?

    Answer: Evaporator outlet superheat

    A TXV meters refrigerant to hold a set superheat at the evaporator outlet.

  3. Where is liquid subcooling measured in a vapor-compression system?

    Answer: At the condenser outlet or liquid line

    Subcooling is the saturated condensing temperature minus the actual liquid line temperature.

  4. How does an air-source heat pump typically defrost its outdoor coil?

    Answer: It reverses the cycle with the reversing valve so the outdoor coil works as a condenser

    Switching briefly to cooling mode sends hot gas to the outdoor coil and melts the frost.

  5. When is a waterside economizer most useful?

    Answer: When outdoor wet-bulb is low enough for tower water to cool the chilled water loop through a heat exchanger

    Cold tower water passes through a plate-and-frame heat exchanger to give free cooling with the chillers off or unloaded.

  6. How does an enthalpy (total energy) recovery wheel differ from a sensible-only wheel?

    Answer: It transfers both sensible heat and moisture between airstreams

    A desiccant coating lets the wheel move moisture as well as heat.

  7. What is a key design benefit of a dedicated outdoor air system (DOAS)?

    Answer: It separates ventilation and latent load handling from the zone sensible cooling equipment

    DOAS conditions all ventilation air on its own, so terminal units can deal mainly with sensible loads.