  1. A breaker fails to close when commanded from the control room but closes manually at the panel. The most likely cause is:

    Answer: Failed remote close relay or control wiring issue

    If local manual close works but remote command fails, the issue lies in the remote control circuit, such as a relay, wiring, or communication link.

  2. Elevated hydrogen gas alone in a DGA sample from a transformer most likely indicates:

    Answer: Corona or partial discharge activity

    Hydrogen as the dominant gas with little methane or acetylene is characteristic of low-energy partial discharge (corona) in transformer insulation.

  3. During a load flow analysis, a feeder shows voltage at the end closer to the substation is higher than near the load. This is abnormal because:

    Answer: Voltage naturally drops along a feeder toward the load end

    Under normal loaded conditions, voltage drops progressively away from the source due to line impedance; a voltage rise toward the load indicates a capacitive source or reverse power flow.

  4. A circuit breaker trips on overcurrent during cold-load pickup after a prolonged outage. The best corrective action is:

    Answer: Temporarily raise the overcurrent relay pickup or use time-delay settings during restoration

    Cold-load pickup causes high initial inrush current; temporarily adjusting relay settings or using time-delay elements prevents nuisance tripping during restoration.

  5. A power transformer's winding resistance test shows one winding is 15% higher than the factory baseline. This suggests:

    Answer: Partial open circuit or deteriorated connection in that winding

    A 15% increase in winding resistance compared to baseline indicates a developing open circuit, poor connection, or deteriorated winding in that tap.

  6. A voltage regulator on a distribution feeder is hunting (continuously adjusting) rather than settling. The most common cause is:

    Answer: Incorrect bandwidth or time-delay settings on the regulator control

    Hunting occurs when the bandwidth is set too narrow or the time delay too short, causing the regulator to continually chase small voltage variations.

  7. A technician finds that a feeder's ground overcurrent relay (51G) operates for every external fault on adjacent feeders. This indicates:

    Answer: CT polarity or wiring is incorrect, causing false zero-sequence current

    Incorrect CT polarity or wiring errors in a residual ground scheme produce spurious zero-sequence current during external faults, causing false relay operation.