  1. During a cable hi-pot DC test, current increases steadily rather than decreasing after initial charging. This indicates:

    Answer: Insulation breakdown or leakage path

    After capacitive charging, current should stabilize or decrease; a rising trend indicates a resistive leakage path or insulation failure.

  2. A transformer oil sample shows elevated acetylene levels in dissolved gas analysis (DGA). This is specifically associated with:

    Answer: High-energy arcing or sparking

    Acetylene is a key indicator of high-energy electrical arcing inside a transformer, distinguishing it from thermal faults.

  3. A protection relay shows 'loss of potential' alarm. Which protection function is most at risk of maloperation?

    Answer: Distance (21) or directional elements

    Distance and directional relays depend on voltage measurements; loss of potential (VT failure) can cause them to see an artificial fault impedance.

  4. A switchgear bus shows intermittent phase-to-ground faults during humid weather. The most likely cause is:

    Answer: Contaminated or tracking insulators

    Contaminated insulators absorb moisture, creating a conductive tracking path that causes intermittent ground faults in high-humidity conditions.

  5. You use time-domain reflectometry (TDR) on a buried cable and see a reflected pulse at 40% of the cable length. This indicates:

    Answer: A fault or impedance discontinuity at that location

    A reflected pulse before the cable end indicates an impedance discontinuity such as a fault, splice defect, or damage at that distance.

  6. A synchronous generator loses excitation while on-line. The immediate electrical effect on the system is:

    Answer: Reactive power absorption and possible voltage depression

    Without excitation, the generator acts as an induction generator and absorbs reactive power from the system, which can depress system voltage.

  7. After replacing a potential transformer fuse, a technician notices the relay still reads zero voltage on one phase. The next diagnostic step is:

    Answer: Verify fuse continuity and check VT secondary wiring connections

    After confirming fuse replacement, verifying secondary circuit continuity and terminal connections is the next logical step before condemning other equipment.