A substation bus voltage drops suddenly but feeder current remains normal. What is the most probable cause?
Answer: Voltage regulator malfunction or tap changer failure
A sudden voltage drop without a corresponding load change typically indicates a voltage regulator or tap changer fault.
When testing a protection CT with a turns-ratio test, you find the measured ratio is 10% higher than nameplate. This most likely indicates:
Answer: Shorted secondary turns
Shorted secondary turns reduce the effective secondary turns, causing the measured ratio to appear higher than the nameplate value.
A ground fault indicator on a distribution feeder activates, but the feeder does not trip. What type of fault is most likely?
Answer: High-impedance ground fault
High-impedance ground faults produce limited fault current that may activate a ground indicator but not exceed overcurrent relay pickup.
You measure negative sequence current in a balanced three-phase system. What does this indicate?
Answer: Phase transposition error or unbalanced fault
Negative sequence current appears when there is phase imbalance caused by an unbalanced fault or wiring error such as a phase transposition.
An automatic recloser operates three times and locks out. The feeder remains de-energized. What is the correct next step?
Answer: Patrol and inspect the feeder for a permanent fault before re-energizing
Lockout after three operations indicates a permanent fault; a physical inspection must locate and clear the fault before re-energizing.
Thermal imaging of a cable termination shows a hot spot at the lug. What should you check first?
Answer: Lug torque and connection integrity
Hot spots at lugs are most commonly caused by loose or improperly torqued connections that increase contact resistance.
A power quality meter records high total harmonic distortion (THD) on a bus supplying a VFD load. The best mitigation is:
Answer: Install a line reactor or harmonic filter
Line reactors and harmonic filters are standard mitigation devices that reduce harmonic currents injected by VFDs into the power system.