Refrigerant Handling and Recovery Flashcards
7 cards from real 313D practice questions. Tap to flip, then mark Knew It or Still Learning — missed cards come back until you master them.
Read the first 7 Refrigerant Handling and Recovery flashcards as text
Under EPA Section 608, what is the maximum allowable leak rate for a residential comfort cooling system containing 50 or more pounds of refrigerant before repair is required?
Answer: 15% per year
EPA Section 608 sets the leak rate threshold for comfort cooling appliances at 15% of the total charge per year before a repair is mandated.
Which refrigerant cylinder color code is used to identify R-410A?
Answer: Rose/pink
R-410A cylinders are color-coded rose/pink per ARI Standard 700 to distinguish them from other refrigerants.
A technician recovers refrigerant into a recovery cylinder that is already at 80% liquid capacity. What should be done next?
Answer: Stop recovery and use a new or properly sized cylinder
Recovery cylinders must never be filled beyond 80% liquid capacity to allow for thermal expansion and prevent dangerous pressure buildup.
What is the primary purpose of the desiccant filter-drier in a recovery machine?
Answer: To remove moisture and contaminants from recovered refrigerant
The filter-drier in a recovery machine removes moisture and particulate contaminants to protect the machine's compressor and valves.
Which of the following refrigerants is classified as an A2L (mildly flammable) refrigerant?
Answer: R-32
R-32 is classified A2L — lower flammability limit above 3.5% by volume and a burning velocity ≤10 cm/s — unlike the A1 refrigerants R-22 and R-410A.
When recovering refrigerant from a system with a known motor burn, the technician should use:
Answer: Recovery equipment equipped with an acid-rated filter to capture contaminants
Acid-laden refrigerant from a burned compressor requires an acid-rated filter in the recovery machine to protect its components and prevent cross-contamination.
According to EPA regulations, technicians must keep records of refrigerant recovery for commercial appliances containing more than how many pounds of refrigerant?
Answer: 20 pounds
EPA Section 608 requires that service records be kept for appliances containing more than 20 pounds of refrigerant, documenting the amount recovered and disposed of.