FREE E2 Commercial Electrical Inspector (NEC) Compliance Questions and Answers

0%

What is the maximum allowable voltage drop for a branch circuit according to NEC recommendations?

Correct! Wrong!

The NEC recommends that the voltage drop for branch circuits not exceed 3%, and the combined voltage drop for feeders and branch circuits should not exceed 5%. This ensures efficient operation of electrical equipment and minimizes energy loss.

When calculating the ampacity of a conductor, which NEC table should be referenced for the baseline ampacity of insulated conductors?

Correct! Wrong!

Table 310.16 provides the ampacities of insulated conductors based on their size, insulation type, and temperature rating. Adjustments for ambient temperature and conductor bundling may apply.

What is the minimum depth required for a direct-buried electrical conduit under a public road?

Correct! Wrong!

According to NEC Table 300.5, the minimum depth for direct-buried electrical conduits under public roadways is 24 inches to protect the conduit from damage by heavy vehicles and road construction.

Which of the following circuits requires GFCI protection in a commercial building?

Correct! Wrong!

NEC Article 210.8(B) mandates GFCI protection for receptacles in specific locations of commercial buildings, including restrooms, kitchens, and areas with sinks, to prevent electric shock.

In a commercial setting, what is the maximum number of disconnects permitted for a service entrance without a main breaker?

Correct! Wrong!

Per NEC Article 230.71(A), a service entrance is allowed to have up to six disconnects, provided they are grouped together. This is commonly referred to as the "rule of six."

Premium Tests $49/mo
FREE February-2025