FREE CDCP Data Center Cooling Questions and Answers

0%

What results in a CRAC unit's low-pressure alarm?

Correct! Wrong!

All of the above options can potentially cause a low-pressure alarm in a CRAC (Computer Room Air Conditioner) unit. Various factors can contribute to low pressure within the cooling system, leading to an alarm condition. These factors include: The belts haven't been adjusted properly, causing a decrease in the efficiency of the system. Blower motor failure, reducing the airflow and affecting the pressure in the unit. Loss of refrigerant, which results in decreased pressure and cooling capacity. Restricted airflow due to factors like blocked vents or obstructions. Dirty filters impeding the airflow and causing pressure imbalances. Each of these issues can disrupt the functioning of the CRAC unit and trigger a low-pressure alarm, indicating that the cooling system is not operating optimally or there's a potential problem that requires attention.

Which of the following benefits of "cold aisle confinement" is NOT one of them?

Correct! Wrong!

"No need for 'tile management'" is NOT a benefit of 'cold aisle containment.' Cold aisle containment is a data center design practice that involves enclosing the cold aisles, where cold air is supplied to the equipment, to prevent mixing with hot air. This containment method helps improve cooling efficiency and overall data center performance.

By putting perforated tiles just in the locations you want to direct cooling, raised floor cooling can assist in providing directed cooling. What is the maximum amount of air perforated tiles can supply?

Correct! Wrong!

The standard volume of air that perforated tiles can provide is typically around "500 to 600 CFM" (Cubic Feet per Minute). Perforated tiles are strategically placed in data center raised floors to allow cold air from the underfloor plenum to be directed toward IT equipment, contributing to effective cooling. The CFM value indicates the rate at which air is delivered through the perforations in the tiles. This value can vary based on factors such as tile design, airflow requirements, and the specific layout of the data center.

What is an example of a compound with a boiling point of 100°F, Compound-X, being in a super heated state?

Correct! Wrong!

An example of Compound-X being in a superheated state would be if it is in a gaseous state with a temperature above its boiling point of 100°F. In this case, if Compound-X is a gas at a temperature of 105°F (which is higher than its boiling point), it would be considered superheated. Superheating occurs when a substance, such as a liquid, is heated above its boiling point without undergoing a phase change into vapor. In the example you provided, Compound-X would be superheated because it's existing as a gas at a temperature greater than its boiling point, without undergoing the transition to a liquid state.

What does "heat density" mean in terms of the HVAC system of a data center?

Correct! Wrong!

"Heat density" in a data center context refers to the amount of heat generated per unit area or volume, usually expressed in watts per square meter (W/m²) or watts per cubic meter (W/m³). It's a measure of how much heat is produced by the IT equipment within a specific space or rack. On the other hand, the "temperature average in an area, but not the entire site" is more accurately described as the ambient temperature or temperature distribution within a specific region of the data center. It's not the same as heat density, which focuses on the amount of heat generated per unit of space.

What is direct exchange (DX) cooling systems' major benefit?

Correct! Wrong!

The biggest advantage of direct exchange (DX) cooling systems is their greater cooling capacity due to direct heat exchange. They achieve this by eliminating the heat transfer losses associated with indirect cooling systems, resulting in higher cooling efficiency and better overall performance.

What follows DOES NOT belong in the "refrigeration cycle"?

Correct! Wrong!

"Aeration" is NOT a component or process in the refrigeration cycle. The refrigeration cycle is a series of thermodynamic processes that allow a refrigeration system to remove heat from a space and transfer it to another location. The main components of the refrigeration cycle include compression, condensation, expansion, and evaporation. These processes work together to achieve the cooling effect in a refrigeration system. "Aeration" typically refers to the process of introducing air into a substance, and it is not part of the standard refrigeration cycle.

What should you check first if your cooling tower alarms for a high water temperature?

Correct! Wrong!

If you receive an alarm on your cooling tower for a high water temperature, the first thing you should check is to "Check to see if the fan is running." The cooling tower's fan is responsible for dissipating heat by drawing in air and facilitating the cooling process. If the fan is not running or functioning properly, it can lead to inadequate cooling and a rise in water temperature. Ensuring that the fan is operational is crucial for maintaining the cooling efficiency of the tower and preventing issues related to high water temperature.

What are the most detrimental effects of having an excessive number of perforated tiles in a datacenter?

Correct! Wrong!

The biggest disadvantage of having too many perforated tiles in a data center is that "it reduces the overall underfloor pressure, while also reducing the overall cooling impact." Perforated tiles are used to allow cold air from the raised floor to flow through and cool the IT equipment. However, having too many perforated tiles can disrupt the balance of airflow and pressure within the data center.

Which of the following statements is not a part of the refrigeration cycle?

Correct! Wrong!

In the basic refrigeration cycle, the refrigerant passes through the evaporator, absorbs heat from the surroundings (air or water), and undergoes a phase change from liquid to vapor (not from vapor to liquid, as mentioned in the statement). This process is known as "evaporating" or "boiling." The refrigerant then enters the compressor, where it is compressed and its temperature and pressure increase. From there, it goes to the condenser, where it releases heat to the external environment and condenses back into a liquid. Finally, the liquid refrigerant passes through an expansion valve or throttle valve, where its pressure is reduced, and the cycle starts again.

What can you do if the top sensor on a rack displays a high temperature alarm?

Correct! Wrong!

If the top sensor on a rack is showing a high temperature alarm, one of the actions you can take is to "Check blanking panel placement." Blanking panels are used to cover empty spaces in a server rack to improve airflow and prevent hot air from recirculating within the rack. If blanking panels are not placed properly or are missing, it can disrupt the airflow and contribute to temperature imbalances within the rack. Checking and ensuring that blanking panels are correctly installed can help improve the rack's overall cooling efficiency and address temperature-related issues.

Which one of these supports cooling via a refrigeration cycle?

Correct! Wrong!

All of these components work together in the refrigeration cycle to achieve the cooling effect.

What PUE is allowed with full EconoPhase operation?

Correct! Wrong!

The lowest possible PUE (Power Usage Effectiveness) in full EconoPhase operation was reported to be around 1.05. EconoPhase is an innovative cooling technology designed to improve energy efficiency in data centers.

Why might utilizing less compressor cooling be more cost-effective than having a cooler maximum temperature in your datacenter?

Correct! Wrong!

When data center temperatures rise and exceed the optimal operating range, computer systems and servers will respond by ramping up their internal fans to dissipate the excess heat. This can significantly impact the overall power consumption within the data center. As the internal fans work harder to cool the systems, they consume more electrical power, leading to increased kW (kilowatt) usage. This can result in higher energy costs and decreased energy efficiency within the data center. Moreover, increased fan usage can also lead to more wear and tear on the equipment, potentially reducing the lifespan and increasing maintenance requirements.

What is the main issue with your HVAC system having too little humidity?

Correct! Wrong!

One of the primary concerns of having too low humidity in an HVAC (Heating, Ventilation, and Air Conditioning) system is "static build-up that can cause major electrical damage." Low humidity levels can lead to an accumulation of static electricity, which poses a risk of damaging sensitive electronic components, including computer equipment, servers, and other electrical devices. This static discharge can potentially cause malfunctions, data corruption, or even catastrophic failures in electronic systems. Maintaining an appropriate level of humidity is important for preventing static-related issues in environments where electronic equipment is present.

What is the main mechanical distinction between computer room air handlers (CRAHs) and CRACs?

Correct! Wrong!

The primary mechanical difference between CRACs (Computer Room Air Conditioners) and computer room air handlers (CRAHs) is that "CRACs have refrigeration compressors as part of their primary system." CRAC units typically include refrigeration compressors in their primary cooling system. These compressors actively cool the air by removing heat from it and then recirculate the cooled air back into the data center or server room environment.

Premium Tests $49/mo
FREE April-2024